Specifications:
| Typical Application: |
Sewage, dewatering |
| Capacities: |
up to
156 GPM
(9.8 LPS) |
| Heads: |
up to
38 ft. (11.6 m) |
| Electrical: |
208V,
1ø, 11.5 FLA, 60Hz; 230V, 1ø, 10.0 FLA,
60Hz; 208V, 3ø, 5.0 FLA, 60Hz; 230V, 3ø,
4.4 FLA, 60Hz; 460V, 3ø, 2.2 FLA, 60Hz; 575V,
3ø 1.7 FLA, 60Hz |
| Motor: |
(single
phase) - 1 HP capacitor start with thermal overload protection,
1750 RPM
(three phase) - 1 HP polyphase, 1750 RPM |
| Intermittent Liquid Temperature: |
140°F (60°C) |
| Minimum
Recommended Sump Diameter: |
Simplex
= 24" (609.6 mm)
Duplex = 36" (914.4 mm) |
Operation:
|
Manual standard
Optional - wide-angle float switch |
| Materials
of Construction: |
Class
30 cast iron |
| Impeller: |
Class
30 cast iron two-vane nonclog |
| Discharge
Size: |
2
NPT (50.8 mm); 3" NPT (76.2 mm) optional |
| Solids
Handling: |
2
(50.8mm) |
| Power
Cord: |
1ø,
20', STW-A; 3ø, 20', STW-A |
| |
|
| Performance: |
 |
Hydromatic reserves the right to make
revisions to its products and their specifications, this catalog
and related information without notice. |